1734-IR2E Allen Bradley Rockwell CompactLogix 5370 I/O Module
1734-IR2E is a POINT I/O Analog Temperature Input Module that features two high-resolution RTD inputs.
HS CODE : 8538909200
Product No :
1734-IR2E 1734IR2EManufacture :
Allen BradleySize (cm) :
5.6 * 7.6 * 1.2Weight (kg) :
0.04Origin :
USAWarranty :
12 MonthLead Time :
Ready StockDescription :
I/O ModuleProduct parameters
Module type: POINT I/O Resistance Temperature Detector (RTD) input module
Number of input channels: 2 single-ended, non-isolated RTD input channels
Input signal range:
RTD: 100 Pt α = 0.00385 Euro (-50...) +320 °C / -58... +608 °F)
Resistance: 0-220 Ω
Resolution: 16-bit, 2.4m Ω/ count, 0.006 °C/ count (Pt385@25 °C) [0.0114 °F/ count (Pt385@77 °F)]
Data format: Signed integer
Conversion type: Delta-Sigma analog-to-digital conversion
Absolute accuracy: 0.1% full scale @ 25 °C (77 °F)
Temperature drift: 30 ppm/°C
Input impedance: >1 MΩ
Power supply:
External DC power supply voltage range: 10-28.8V DC, nominal 24V DC
Maximum POINTBus current: 220 mA @ 5V DC
Power consumption:
Maximum power dissipation: 1.0 W @ 28.8V DC
Maximum heat dissipation: 3.3 BTU/hr @ 28.8V DC
Isolation voltage: 50V (continuous), test voltage is 2550V DC for 60 seconds
Installation method: DIN rail installation (It is recommended to use galvanized yellow chromium steel rail)
Wiring method: Detachable terminal block (RTB). It is recommended to use 0.25-2.5mm ² (22-14 AWG) shielded copper wire, with a rated temperature of 100°C (212°F) and an insulation thickness of 1.2mm
Terminal screw torque: 0.8 N·m (7 lb·in)
Operating temperature range: -20°C to 55°C (-4°F to 131°F)
Storage temperature range: -40°C to 85°C (-40°F to 185°F)
Protection grade: Open type (no enclosure, IP20)
Compatible terminal bases: 1734-TB, 1734-TBS, 1734-TOP, 1734-TOPS
Key switch position: 3
Supported networks: ControlNet, DeviceNet, EtherNet/IP and other open networks
Certification standards: C-TICK, CCC, CE, CUL, GOST, IECEx, KC, MARINE, UL
Relative humidity: 5-95% (non-condensing)
Vibration: 5 g @ 10-500 Hz during operation
Impact: 30 g during operation, 50 g during non-operation
Function
RTD input processing
Supports 2 single-ended, non-isolated channels, compatible with 100 Pt α = 0.00385 Euro RTD sensor (-50... +320 °C / -58... +608 °F and 0-220 Ω resistance signal.
The analog signal is converted to a 16-bit signed integer through the Delta-Sigma converter to provide high-resolution temperature or resistance measurement (2.4 mΩ/ count, 0.006 °C/ count).
High resolution
Compared with 1734-IR2, 1734-IR2E offers higher resolution and is suitable for higher-precision temperature measurement applications.
Diagnostic function:
Provide channel-level diagnosis, including over-range/under-range, ultra-high/high/low/ultra-low alarms and open circuit detection.
Diagnostic data is stored in 16-bit registers and can be used for local monitoring or integrated into HMI, SCADA or DCS systems.
Flexible configuration
Supports multiple temperature units and user-defined units (mV).
Channel parameters can be independently configured, including sensor type, temperature unit, engineering unit scaling, and alarm threshold.
Modular design
Compatible with POINT I/O communication adapters and supporting distributed I/O architectures.
Detachable terminal blocks (RTB) simplify wiring and maintenance.
Compact and efficient
Compact in size, it is suitable for control cabinets with limited space.
Low power consumption design (1.0W) reduces energy consumption.
Status monitoring: Equipped with status indicator lights for modules, networks and input channels, it facilitates real-time monitoring and fault diagnosis.
No external power supply required: No additional DC power supply is needed, simplifying system design.
Application scenarios
Industrial automation: Used in PLC or PAC systems to monitor temperature or resistance signals, suitable for factory production lines and equipment status monitoring.
Process control: In industries such as chemical engineering, oil and gas, pharmaceuticals, and water treatment, it precisely measures temperature (such as in reactors, storage tanks, and pipelines) or resistance signals.
Manufacturing industry: In industries such as automotive manufacturing, food and beverage, and packaging machinery, monitor process temperatures to ensure production quality.
Distributed I/O system: In large factories, combined with POINT I/O communication adapters, it reduces wiring costs and enhances system flexibility.
High-precision temperature monitoring: Due to its high resolution, it is suitable for applications that require precise temperature measurement, such as laboratory equipment or precision manufacturing.
Equipment condition monitoring: It is used for predictive maintenance to monitor the temperature changes of motors, pumps or other equipment and prevent malfunctions.
Space-constrained environments: The compact design is suitable for installation on small control cabinets or DIN rails close to on-site equipment.
Advantage Products:
DANFOSS | VLT® AutomationDrive,Plus+1®,MCP | ||
KEYENCE | KV-800,KV-300,KP-3000,KP-7000,KJ,KV-Nano,HMI | ||
GE FANUC | PACSystems RX3i,90-30,90-70 | ||
SCHNEIDER | Modicon M340,Modicon M580,Modicon X80,Pioneer | ||
BENTLY NEVADA | 3500/94,3500/53,3500/22M,3500/42M,330180-90-00 | ||
HONEYWELL | Experion® PKS,ControlEdge™ ,HC900 | ||
ALLEN BRADLEY | CompactLogix,ControlLogix, MicroLogix,Flex I/O | ||
WESTINGHOUSE | Westinghouse Modbus,Westinghouse 9080,Westinghouse 8000,Westinghouse 1000 |
All items are Distributor Ready-stock Genuine Brand-new Supplying, please inform us if the other conditions are needed, Used, Open-box, Refurbished, etc.
Many Available just wait for you, feel free to ask to get better deal!!!
Bou L(Sales Manager)
Tina(Sales Specialist)
Ricardo(Sales Specialist)
Tel:+86 18359251915
Doris(Sales Specialist)
Tel:+86 13599531915
Conditions |
Original Brand New |
Approximate Lead Time |
3-5 days |
Warranty |
One Year |
Online Service |
24 / 7 |
Express Company |
DHL / FedEx / UPS / TNT etc. |
MOQ |
1 Piece |
TZ Tech is not an authorized surplus dealer or affiliate for the Manufacturer of this product.
The product may have older date codes or be an older series than that available direct from the factory or authorized dealers. Because TZ Tech is not an authorized distributor of this product, the Original Manufacturer’s warranty does not apply.
While many PLC products will have firmware already installed, TZ Tech makes no representation as to whether a PLC product will or will not have firmware and, if it does have firmware, whether the firmware is the revision level that you need for your application.
TZ Tech also makes no representations as to your ability or right to download or otherwise obtain firmware for the product from Rockwell, its distributors, or any other source.
TZ Tech also makes no representations as to your right to install any such firmware on the product.
TZ Tech will not obtain or supply firmware on your behalf. It is your obligation to comply with the terms of any End-User License Agreement or similar document related to obtaining or installing firmware.
Sitemap | Blog | XML | Privacy Policy
In addition, with your permission, we want to place cookies to make your visit anointeraction with slOC more personal. For this we use analytical and advertisingcookies. With these cookies we and third parties can track and collect yourinternet behawior inside and outside super-instrument.com. With this we and third parties adapt super-instrument.com and advertisementsto your interest. By clicking Accept you agree to this. If you decline, we only usethe necessary cookies and you unfortunately will not receive any personalizedcontent. Please visit our Cookie policy for more information or to change yourconsent in the future.
Accept and continue Decline cookies