1756-IA32 is a digital input module that is part of the ControlLogix family of I/O modules.
HS CODE : 8538909200
Product No :
1756-IA32 1756IA32Manufacture :
Allen BradleySize (cm) :
14 * 10* 14Weight (kg) :
0.1Origin :
USAWarranty :
12 MonthLead Time :
Ready StockDescription :
I/O ModuleProduct parameters
Input channel:
Quantity: 32 digital input channels, divided into 2 groups, with 16 channels in each group.
Input type: AC digital input.
Voltage range: 74-132V AC, frequency 47-63 Hz.
Nominal input voltage: 120V AC, 50/60 Hz.
Isolation: Inter-group isolation (16 channels per group), input to backplane isolation, no inter-channel isolation.
Electrical characteristics:
Open-state current
Maximum 15 mA @ 132V AC.
Minimum 5 mA @ 74V AC.
Closed-state characteristics:
Maximum voltage: 20V AC.
Maximum current: 2.5 mA.
Surge current: Maximum 390 mA, duration decays to below 37% within 22 ms without activation.
Backplane current
5.1V DC: 165 mA.
24V DC: 2 mA.
Total backplane power: 0.9W.
Power dissipation: Maximum 6.1W at 60°C.
Heat dissipation: 20.8 BTU/ hour at 60°C.
Isolation voltage: 250V AC (continuous), basic insulation type, input to the backplane and isolation between groups.
Input delay time:
OFF to ON
Hardware latency: Nominal 1.5ms, maximum 10ms.
Users can configure the filtering time: 1 ms or 2 ms.
ON to OFF
Hardware latency: Nominal 1 ms, maximum 8 ms.
Users can configure the filtering time: 9 ms or 18 ms.
Physical properties:
Installation method: Rack-mounted, compatible with ControlLogix racks (such as 1756-A4, A7, A10, A13, A17).
Terminal block: Compatible with detachable terminal blocks (RTB), such as 1756-TBCH (36-pin screw terminal) or 1756-TBS6H (36-pin spring clip terminal).
Pre-wired cables: Support Bulletin 1492 pre-wired cables (1492-IFM40F, 1492-IFM40D120A-2, 1492-IFM40F-2).
Enclosure type: Open type (IP20 protection grade).
Display: The front panel of the module has LED indicator lights for input, communication status and module health status.
Environmental conditions:
Operating temperature: 0°C to 60°C
Storage temperature: -40°C to 85°C.
Relative humidity: 5% to 95% (non-condensing).
Vibration: 2G (10-500 Hz).
Operating impact: 30G.
Non-operational impact: 50G.
Surge immunity: The signal port can withstand surges from 2 kV lines to ground.
Certification:
Compliant standards: CCC, CE, CSA, KC, MARINE, NRTL, RCM, UL.
Programming and Configuration
Compatible software: Studio 5000 Logix Designer, used for module parameter setting and programming.
Function
High-density input: It offers 32 input channels, making it suitable for applications that require monitoring a large number of digital signals. Compared with the 1756-IA16I (16 channels, with inter-channel isolation), the 1756-IA32 has a higher channel density but no inter-channel isolation, making it suitable for general input requirements.
Flexible communication format:
Support multiple data formats:
Standard input data format: Only return fault and input data.
CST timestamp input data format: Return the input data and the changed timestamp.
Rack-optimized data format: Collect digital word data from remote racks and convert it into rack images.
Only listen in mode (including standard, CST timestamp and rack-optimized format).
Input information and output status can be shared with the ControlLogix controller via EtherNet/IP or ControlNet network.
Diagnosis and Status Monitoring
It is equipped with LED diagnostic indicator lights to display the module status, input status and communication health status, facilitating on-site fault investigation.
Support user-configurable filtering time, optimize input signal processing, and adapt to different response speed requirements.
Modular design
The on-site wiring is connected through detachable terminal blocks (RTB) or 1492 interface modules (IFM), which is convenient for installation and maintenance.
Supports rack-mounted installation and can be integrated into local or distributed ControlLogix racks.
Support multiple input devices:
Compatible with a variety of AC input devices, such as buttons, limit switches, proximity sensors, etc., and supports sinking/sourcing configuration.
High reliability
The design meets the requirements of industrial environments, is resistant to high temperatures, high humidity and vibration, and is suitable for demanding industrial applications.
Inter-group isolation ensures that even if one group of channels fails, the other group can still work normally.
Application scenarios
Manufacturing industry: It is used to monitor digital signals on production lines, such as the status of buttons, sensors and switches, and is suitable for high-density input scenarios such as automotive manufacturing and electronic assembly.
Process control: Applied in the chemical, oil and gas, pharmaceutical and food and beverage industries, it monitors the on/off status of valves, pressure switches or other process equipment.
It is suitable for scenarios that require rapid reading of digital input, such as process status detection.
Machine status monitoring: It is used to read the status of limit switches, buttons or proximity sensors, track the operating status of equipment, and ensure the smooth operation of the production line.
Safety interlock: Detect the status of the emergency stop button or safety sensor in the safety system to trigger a safety interlock or stop the operation.
Counting application: It is used for counting objects passing through sensors, such as product counting on packaging lines, and is suitable for high-frequency input signal processing.
Distributed control system: Integrated into distributed I/O systems via EtherNet/IP or ControlNet networks, it is suitable for large factories or remote monitoring applications.
Traditional system maintenance: 1756-IA32 is often used for the maintenance or expansion of existing ControlLogix systems, especially suitable for scenarios that require high-density input but do not need isolation between channels.
Advantage Products:
DANFOSS | VLT® AutomationDrive,Plus+1®,MCP | ||
KEYENCE | KV-800,KV-300,KP-3000,KP-7000,KJ,KV-Nano,HMI | ||
GE FANUC | PACSystems RX3i,90-30,90-70 | ||
SCHNEIDER | Modicon M340,Modicon M580,Modicon X80,Pioneer | ||
BENTLY NEVADA | 3500/94,3500/53,3500/22M,3500/42M,330180-90-00 | ||
HONEYWELL | Experion® PKS,ControlEdge™ ,HC900 | ||
ALLEN BRADLEY | CompactLogix,ControlLogix, MicroLogix,Flex I/O | ||
WESTINGHOUSE | Westinghouse Modbus,Westinghouse 9080,Westinghouse 8000,Westinghouse 1000 |
All items are Distributor Ready-stock Genuine Brand-new Supplying, please inform us if the other conditions are needed, Used, Open-box, Refurbished, etc.
Many Available just wait for you, feel free to ask to get better deal!!!
Bou L(Sales Manager)
Tina(Sales Specialist)
Ricardo(Sales Specialist)
Tel:+86 18359251915
Doris(Sales Specialist)
Tel:+86 13599531915
Conditions |
Original Brand New |
Approximate Lead Time |
3-5 days |
Warranty |
One Year |
Online Service |
24 / 7 |
Express Company |
DHL / FedEx / UPS / TNT etc. |
MOQ |
1 Piece |
TZ Tech is not an authorized surplus dealer or affiliate for the Manufacturer of this product.
The product may have older date codes or be an older series than that available direct from the factory or authorized dealers. Because TZ Tech is not an authorized distributor of this product, the Original Manufacturer’s warranty does not apply.
While many PLC products will have firmware already installed, TZ Tech makes no representation as to whether a PLC product will or will not have firmware and, if it does have firmware, whether the firmware is the revision level that you need for your application.
TZ Tech also makes no representations as to your ability or right to download or otherwise obtain firmware for the product from Rockwell, its distributors, or any other source.
TZ Tech also makes no representations as to your right to install any such firmware on the product.
TZ Tech will not obtain or supply firmware on your behalf. It is your obligation to comply with the terms of any End-User License Agreement or similar document related to obtaining or installing firmware.
Sitemap | Blog | XML | Privacy Policy
In addition, with your permission, we want to place cookies to make your visit anointeraction with slOC more personal. For this we use analytical and advertisingcookies. With these cookies we and third parties can track and collect yourinternet behawior inside and outside super-instrument.com. With this we and third parties adapt super-instrument.com and advertisementsto your interest. By clicking Accept you agree to this. If you decline, we only usethe necessary cookies and you unfortunately will not receive any personalizedcontent. Please visit our Cookie policy for more information or to change yourconsent in the future.
Accept and continue Decline cookies